| A |
Status LED’s:
There are Four Status LED’s on the C277.
·
COM stands for
Communication. It will flash
any time a communication packet passes to or from the C277.
·
COP stands for
Controller Operating Properly. It
will flash every half-second if the internal CPU is functioning properly.
This light should start flashing as soon as power is supplied to
the PWR1 connection.
·
PWR1 stands for
Power 1. This light will turn
on when power is properly applied to the Pins B+ and B-. This is the control power.
·
PWR2 stands
for Power 2.
This lights when the internal (minus) 5 VDC supply is functioning
properly. |
| B |
RS-485
Communication Port: Port A, Port B, and Port C are electrically
common, for wiring convenience.
If more than one module is used, you can bring your patch cable
into Port A and then connect from Port B to the next module.
Note:
The last module in the communication chain must have a terminating
resistor module. Port C is used in environments that require a screw-down
terminal for connection. |
| C |
MODBUS
Address Select Shunts: These shunts allow you to assign a unique
address to each C277 that may be in the system.
This allows the master controller to differentiate between the
modules.
For example, to name the controller address 21, place the shunts on
LK1, LK4, and LK16 (1+4+16 = 21). |
| D |
Control
Power Terminals:
Hook battery (+) to the terminal labeled B+. Hook battery (-) to the
terminal labeled B-. |
| E |
Channel
Connection Terminals: Each channel has two dedicated terminals.
The top row is the negative side of the connection and the bottom
row is the positive side of the connection. |
C277 Description
The C277 is a member of the Ryeso Comm Series of controllers.
It adds temperature-sensing capability to existing and future Ryeso
Controllers via MODBUS RTU communication via an RS-485 port. It can read up to 18 thermocouples and/or mA sources.
|
C277 Specifications
| Input Voltage |
9 to 28 VDC |
| Operating Temperature |
-22 to 158 °F (-30 to 70 °C) |
| Storage Temperature |
-22 to 158 °F (-30 to 70 °C) |
| Communications: |
1 RS-485 9600-N-8-1 Communication port with multiple connection
types. |
| Inputs |
18
– Can be configured to read thermocouples or end of line 0-24 mA
(4-20mA) signals |
For more detailed information on this platform, please click here.
|